中文字幕永久在线-中文字幕一二三区-国产哺乳奶水91在线播放-99热国产-日韩精品福利-五月精品-国产又粗又长视频-在线观看亚洲天堂-成人国产三级-天天操夜操-国产又粗又猛又爽又黄av-avtt中文字幕-激情黄色av-性欧美17一18内谢-欧美日韩中文在线观看-久中文字幕-色小妹av-中文字幕资源站-jul023被夫上司连续侵犯-欧美一级黄色片在线观看

Company News

當前位置:首頁 >>Company News

The valve is unstable

發布時間:2018-11-13 關注次數:

The valve is unstable

The symptoms and causes are as follows:

1. The gas source pressure is unstable. 1 The compressor capacity is too small; 2 The pressure reducing valve is faulty.

2. The signal pressure is unstable. 1 The time constant of the control system (T=RC) is not appropriate; 2 The regulator output is unstable.

3. The air supply pressure is stable and the signal pressure is stable, but the action of the regulating valve is still unstable. 1 The ball valve of the amplifier in the positioner is not tightly worn by the dirt, and the output oscillation occurs when the gas consumption is particularly increased; 2 the nozzle flapper of the amplifier in the positioner is not parallel, the baffle cover cannot cover the nozzle; 3 output tube The line is leaking; 4 the rigidity of the actuator is too small; 5 the frictional resistance is large in the movement of the valve stem, and there is a blockage in the contact part.


Control valve selection

Selection of structural form: steam flow control should select single valve seat; large diameter, large flow, low pressure difference should choose butterfly valve, but the leakage is large at this time; when the medium is high pressure, high pressure regulating valve should be selected; Sewage, prevent valve blockage, optional angle control valve; optional three-way control valve for water volume or water temperature adjustment of heat exchanger.


微信公眾號